4.6.3 MA Remote Controller/ME Remote Controller in Combination
with Lossnay M-NET Remote Controller
System
The MA remote controller, ME remote controller, and Lossnay M-NET remote controller can be used in combination.
Combination of Air Conditioner Remote Control and Lossnay Remote Control
Indoor Unit
Model for MA remote control (Type C or later)
Model for other than MA remote control (Type B or earlier)
« :
× :
Compatible
Incompatible
System Examples: 1
Setting Method
(1) Make the Group setting for the indoor unit.
(2) Make the Group setting for the Lossnay unit.
(3) Set the indoor unit and Lossnay unit in interlocked operation.
When using the centralised controller, make both the Group setting and operation setting for the previously mentioned units.
Though the MJ-180A cannot set interlocked settings, it should set at MA/ME remote controllers.
Characteristics
(1) When the indoor unit is set for interlocked operation in 1 group:
Interlocked operation with the indoor unit from the air conditioner remote controller is possible and can switch between
High/Low/Off.
From the air conditioner remote controller it is possible to switch the Lossnay only between High/Low/Off.
From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
(2) When the 2 or more indoor units with different group are set for interlocked operation, the Lossnay will operate if at least 1
group operates. The Lossnay will stop operation if all groups stop operation.
From an air conditioner remote controller it is possible to switch the Lossnay only between High/Low when other groups are
operating.
From the Lossnay remote controller it is possible to switch the Lossnay between High/Low/Off.
Note:
If the display on the MA remote controller/ME remote controller, or other air conditioner remote controller, is cancelled, the air
conditioner remote controller will not show the ventilation display even if you operate the Lossnay from the Lossnay M-NET
remote controller.
Note:
Transmission cable power control for indoor units
Be sure usage is within the following boundaries.
Indoor units + ME remote controllers (compact remote controllers) + Lossnay M-NET remote controllers is less than or equal
to 40 units.
Indoor units are less than or equal to 20 units.
(The numbers of MA remote controllers and Lossnay units are not included in the above number of units.)
124
Centralised
controller
Power
Outdoor unit
supply
(201)
(051)
unit
Lossnay LGH-RX type
Interlocked operation setting
Indoor
Lossnay
unit (001)
(002)
MA remote
Lossnay M-NET
controller
remote controller
(101)
PZ-52SF-E (102)
Group1
Group2
«
×
( ) address