4. Troubleshooting
Troubleshooting by alarm code
C1-26
Alarm code
Alarm stop reason
Thermistor for detection of temperature of gas suctioned (Ts) by compressor indicates an abnormal value.
PCB monitoring position
PCBd (I/O PCB) CN27
N O T E
Refer thermistor characteristics chapter.
measure thermistor resistance. 
109
SMGB0097 rev.0 - 07/2015
Suction Gas THM Abnormality (CN27)
The connection and 
insertion of connector
CN27 on PCB
 (I/O PCB) 
d
are correct
Yes
Remove the 
connectors and
Is resistance value
normal?
Yes
No
Correction of connections
No
Replace thermistor
Replace PCB
(I/O PCB) 
d
4