Selection Of Enabling/Disabling Of Alarm Release By Means Of Remote Stop - Hitachi SAMURAI Series Service Manual

Condenserless water chillers
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

2. Control Functions
Control functions on the module

Mode selection method
Select "10 minutes"

2.1.16 Selection of enabling/disabling of alarm release by means of remote stop

The release of an alarm in case that the chiller unit has stopped due to an alarm is achieved by stop control (it is possible to 
stop both from the stop button of the main unit or from remote stop control). But it is possible to configure this alarm release 
to make it valid only from the stop button on the main unit (alarm cannot be released by remote stop control). This function 
is valid for places where there is a remote device for automatic stop order when an alarm is emitted.
Select dissable
34
SMGB0097 rev.0 - 07/2015