4. Troubleshooting
Troubleshooting by alarm code
40-40
Alarm code
Alarm stop reason
The  connection  of  wiring  for  transmission  between  modules  (Transmission  line  between  master  and  slaves)  and  the 
transmission wiring for connection of group controller is mixed. 
Retry indication
No retry
PCB monitoring position
PCBc (CPU PCB) CN2 (Transmission port between modules)
 PCBc (CPU PCB) CN300 (Transmission port for group controller)
6E-6E
Alarm code
Alarm stop reason
Suspension of water supply protection switch is activated.
PCB monitoring position
PCBc (CPU board) PCN10
Hot-and-chilled water 
is flowing with an amount 
of flow higher than the usage 
Remove the wiring 
attached to connector PCN10 
on PCBc (CPU PCB) and check 
conductivity. Is there any 
The connection and 
insertion of connector PCN10
on PCBc (CPU PCB) are 
Check of PCBc 
120
SMGB0097 rev.0 - 07/2015
Transmission abnormality (Miswiring)
The connection of 
transmission wiring is 
correct
Yes
Check PCBc (CPU PCB)
Cold Water Suspension  (Option)
No
range
Yes
No
conductivity?
Yes
No
correct
Yes
(CPU PCB)
No
Connect transmission wiring 
correctly
Check the pump
Check the pump flow
Clogging of water 
Check the water outage 
protection switch
Check of wiring