2. Control Functions
Control functions on the module

2.1.5 Prevention of simultaneous startup

This function prevents simultaneous startup when supplying power to multiple units (in case that all modules are working 
individually, not in a master-slave group)
In case that multiple chiller units are installed, it may be thought that all of them will start operation simultaneously when 
3  minutes  have  passed  after  entering  in  recovery  from  power  interruption.  (Note:  When  using  the  function  to  control 
the number of units, simultaneous startup is prevented by performing sequential startup automatically. ) To prevent this 
phenomenon, it is possible to shift the settings of time guard (3 minutes).

Setting method
By means of DIP switch setting (DSW3-1#, 3-2# ,3-3#), the following number of seconds are added to the time guard (3 
minutes). 
DIP  switches  (DSW3-1#,  3-2#,  3-3#)  are  used  for  address  setting  when  using  the  functions  to  control  the  number  of 
units, but the addition of time to the 3-minutes guard is effective even if these functions are not used. In this case, it is not 
necessary to connect transmission cables between each chiller unit. )
DSW3 (PCB
Unit No.
#1
#2
1
OFF
OFF
2
OFF
OFF
3
OFF
ON
4
OFF
ON
5
ON
OFF
6
ON
OFF
7
ON
ON
8
ON
ON

2.1.6 Reverse prevention control

The state of three-phase input is detected in this chiller unit, and it does not operate in case of reverse or open phase.
Three-phase input 
detection
16
SMGB0097 rev.0 - 07/2015
)
Added
A
time
#3
#4
OFF
OFF
0 s
ON
OFF
5 s
OFF
OFF
10 s
ON
OFF
15 s
OFF
OFF
20 s
ON
OFF
25 s
OFF
OFF
30 s
ON
OFF
35 s
Reverse
phase
(Open R phase)
Open phase
(Open S phase)
(Open T phase)
Example: When setting 2 chiller units as unit 1 and unit 2, 
upon  recovery  from  momentary  power  interruption  unit  1 
restarts after 3 minutes and unit 2 restarts after 3 minutes
and 5 seconds.
N O T E
Power reactivation needed
Alarm display "Reverse/open phase"
Alarm display "Reverse/open phase"