3. Servicing
Cycle components

3.3.6 Filter drier

There are two possible main maintenance operations to do with the filter drier: the substitution of the inner core due to its 
adsorption saturation or the substitution of the whole unit due to some damage.

Solid core substitution
Follow the next steps in order to proceed to replace the inner core of the filter drier:
1 Remove the 8 screws (1) that fixes the top cov-
er (2). Carefully, remove the spring (3), the top 
cover gasket (4), the wing nut (5) and the lock 
washer (6). 
2 Retire the top plate (7) and then the felt gasket 
(8)
3 Take  the  solid  core  (9)  out  and  proceed  to  the 
replacement.
4 When  reassembling  after  replacing  the  solid 
core, perform the procedure in the reverse order 
than removing.
N O T E
At reassembling, oil or grease the top cover gasket
and the thread of the cover screws.

Filter drier unit replacement
Replace the filter drier unit if any leakage or malfunction is detected. Proceed following the steps explained below:
1 Protect  the  surroundings  of  the  unit  from  the 
heat of the blowtorch.
2 Remove the brazed parts using a blowtorch and 
previously  cooling  the  pipe  side  and  the  filter 
drier unit with wet cloth in order to avoid brazing 
material enter inside the pipes.
3 Unscrew the nuts of the clamping bracket to re-
lease the filter drier.
C A U T I O N
After blowtorch operations, filter drier and the sur-
roundings may be too warm. Take special care to
use insulation protection.
71
SMGB0097 rev.0 - 07/2015
1
2
3
4
5
6
7
Front view
Rear view
Brazed parts
8
9
Brazed parts
Clamping bracket
Clamping bracket