4. Troubleshooting
Pressure sensor characteristics

4.11 Pressure sensor characteristics

4.11.1 High-pressure sensor

4.11.2 Low-pressure sensor

4.12 Procedures for trouble

The following table shows efficient checking procedures for trouble.
Fault
Interlock Circuit for Chilled Water Pump is Open
Compressor does not
operate
Electrical Protective Devices Are Tripped.
Incorrect Wiring Connection for Compressor Power 
Source
Excessively High Discharge Pressure
Compressor stops on
high pressure switch
Malfunction of High Pressure Switch
Excessively High Discharge Pressure and Suction 
Pressure
High or low voltage, single-phase or phase 
imbalance
Compressor stops on
overcurrent relay
Loose connection
Faulty Compressor Motor
Faulty Overcurrent Relay
126
SMGB0097 rev.0 - 07/2015
4.5
2.5
0.5
0
2.5
4.5
2.5
0.5
(0.3)
(-0.1)
0
1.0
Possible Cause
5.0
(Mpa)
(Mpa)
2.0
Check/Corrective Action
1.    C heck the pump contactor. Repair or replace, if 
necessary.
2.  Check for the faulty pump.
Remove the causes, and reset the "ON" button. 
See the following causes.
Interchange two of three terminals R, S and T at the 
main power source terminals.
See
High Discharge Pressure
Readjust the setting or replace, if defective.
See
High Discharge Pressure
Pressure.
Check the power supply line and contactors. 
Repair, if necessary.
Tighten the loose electrical connection or repair, if 
necessary.
Check the compressor motor. Repair or replace, if 
necessary.
Replace it, if necessary.