3. Servicing
Cycle components
2 Remove  the  2  Victaluic  connections  from  the 
water connections.
3 Screw eyebolts to both sides of the cooler to the 
bolts  for  that  purpose.  Fasten  a  textile  belt  to 
proceed to lift the cooler. 
C A U T I O N
Do not never use chains or metallic ropes to lift the
cooler as they can damage it.
4 Unscrew  the  4  screw  of  the  foot  plate  heat 
exchanger.
5 Remove  de  cooler.  Softly  lift  the  cooler  and 
place it on a strong and stable surface.
C A U T I O N
In spite of water shut-off valves are closed,
water inside the plate heat exchanger and
water pipe remain.
C A U T I O N
Plate heat exchanger is heavy, two persons
and a portable crane or similar are required.
69
SMGB0097 rev.0 - 07/2015
2 Screws
Victaulic 
connections
3
2 Screws