15.3 ME Remote Controller (PAR-F27MEA)
15.3.1 Operating Lossnay with ME remote Controller
(When Interlocked with City Multi Indoor Unit)
Operation method is same as A-control remote controller. Refer to page C-100.
15.3.2 Initial registration mode
Register the address of the indoor unit with the remote controller.
1 Stop the remote controller by pressing the [ON/OFF] button.
•
If the indoor unit is not registered, "HO" appears in the room temperature display. Follow step 2.
2 Display "INDOOR UNIT ADDRESS NO."
•
Press and hold down the [FILTER] button (shown as
seconds.
15.3.3 Interlocked registration
3 Display the "OA UNIT ADDRESS NO."
•
Press the "Operation mode" button (shown as
Press once again to return to "INDOOR UNIT ADDRESS NO." shown in Step 2.
INDOOR UNIT
ADDRESS NO.
•
Use the
and
•
Use the
and
tered.
CENTRALLY CONTROLLED
AUTO OFF
STAND BY
C
DEFROST
G
PAR-F27MEA
E
INDOOR UNIT
ADDRESS NO.
G
).
OA UNIT ADDRESS NO.
[TEMP] buttons (shown as
[TIMER SET] buttons (shown as
INDOOR UNIT
ADDRESS NO.
F
1Hr.
DAILY
ON OFF
CLOCK
REMAINDER
FILTER
CHECK MODE
TEST RUN
LIMIT TEMP.
ERROR CODE
NOT AVAILABLE
TEMP.
ON/OFF
CLOCK→ON→OFF
FILTER
CHECK TEST
TIMER SET
H
B
D
A
) and the "Louver" button (shown as
Both "INDOOR UNIT ADDRESS NO." and "OA
UNIT ADDRESS NO." will appear simultaneously.
C
) to select the address of the indoor unit to be interlocked.
H
) to select the address of the Lossnay unit to be regis-
OA UNIT ADDRESS NO.
A
B
) simultaneously for two
C-103