Signal cables from external devices (Table 1-1-3)
Check the following checkpoints when connecting with level signal/pulse signal output devices, and Mr. Slim units.
No.
1
Do the transmission cables meet regulations? (Type, diameter)
2
Is the signal cable wired at least 5 cm away from the power supply cable?
3
Are multiple transmission or signal cables wired to the same power cable
duct?
4
Are multiple signal cables wired with multi core cables?
5
Are the signal cables securely connected to the terminals?
6
Are the signal cables connected to the specified terminal blocks?
Mr. Slim control signal
Charged signal
Uncharged a-contact signal: TM2 1, 3
7
Is the wiring length of the signal cable within the regulations?
Mr. Slim control signal
Charged signal
Uncharged a-contact signal: Total extension within 500 m
8
Do the external signals meet specifications?
Level signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
Pulse signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
(A pulse width of 200 ms or greater is required)
9
Are the type of input signal and the setting of the pulse input matched?
Pulse signal
Other than pulse signal: OFF setting
10
In a system with multiple Lossnay units, are the signal cables connected to
the specified Lossnay unit?
Basic system (PZ-60DR-E, PZ-41SLB-E):
Lossnay unit for which the Main/Sub selection switch (SW1) is set to "Main"
M-Net control:
Lossnay unit that is set to the address with the smallest number within the group
11
When PZ-60DR-E is not used, are the function selection switches (SW2,
SW5) on the Lossnay circuit board set correctly?
12
When PZ-60DR-E is used, is the function selection set correctly?
C-46
Checkpoint
: TM2 1, 2
: TM2 1, 2
: Total extension within 500 m
: Within limitation of the external device
: ON setting
Action
Use specified cables.
Wire the signal cable at least 5 cm
away from the power supply cable.
Wire the transmission cables away
from the signal cables.
Using suitable cables, wire the sig-
nal cables so that they are separat-
ed from one another.
Connect them securely.
Connect them to the specified termi-
nal blocks.
Wire within the regulations.
Input a signal that suits the specifi-
cations.
<When using PZ-60DR-E>
Check the pulse input setting from
the function selection. (Refer to page C-63)
<When not using PZ-60DR-E>
Check the setting of the pulse input
switch (SW2-2) on the Lossnay cir-
cuit board. (Refer to page C-63)
Connect the signal cables to the
specified Lossnay unit.
Set the switches correctly to corre-
spond with the application.
(Refer to page C-72)
Set it correctly to correspond with
the application.
(Refer to page C-78 to C-90)