1 When using PZ-60DR-E or PZ-41SLB-E to connect multiple Lossnay units
● Connect the sensor to the Lossnay set to "Main".
● It is not necessary to connect to any Lossnay with the "Sub" setting.
● Connect any sensor, etc., with the external change input to the Lossnay unit set to "Main".
● Any Lossnay with the "Sub" setting will operate at the same High/Low setting as the Lossnay with the "Main" setting
when there is sensor signal input.
2 When using M-NET for a group of multiple units
● Even if the units are in the same group, you can only change operation to High/Low for Lossnay units connected to the
sensor.
CASE 1 : PZ-60DR-E
Main
PZ-60DR-E
Note:
● When using the M-NET system, the fan speed being input by the sensor signal will not be displayed on the remote controller.
5.10 When switching By-pass externally
Establish the wire connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16 (Ventila-
tion mode selector).
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
5.11 When using the remote/local switching and
the ON/OFF input (level signal)
The remoto controller (PZ-41SLB-E) cannot be used.Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in CN32 on
the Lossnay control PCB.
Remote control
circuit
Relay circuit
SW2
X
X
SW1
Y
Y
PZ-60DR-E or PZ-41SLB-E
Sub
Sub
Lossnay
Lossnay
Lossnay
CO
sensor
2
Group
Remote display
adaptor (Optional)
PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Y
ellow 4
SW1
Green 5
Not used. Insulate completely .
Max wiring length 10 m
Remote ON/OFF
adaptor
Lossnay control
(PAC-SE55RA-E)
board
Orange 1
CN32
Red 2
Brown 3
Max wiring length 10 m
Main
Sub
Lossnay
Lossnay
(Main)
(Sub)
CO
sensor
2
CASE 2 : PZ-52SF-E
PZ-52SF-E
With SW1 is "ON", the ventilation mode of Lossnay is
Lossnay
changed to the By-pass ventilation regardless of the setting
control board
on the remote controller.
CN16
* When the outdoor air temperature drops lower than 8°C, it
changes to the heat exchanger ventilation. (Display of the
remote controller does not change.)
Fan speed/
Ventilation
mode selection
SW1: When this is ON, Lossnay cannot turn ON/OFF by the
Remote Controller (PZ-60DR-E, PZ-52SF-E).
SW2: When SW1 is ON, Lossnay can be turned ON by set-
ting SW2 at ON or turned OFF by setting SW2 at
OFF.
SW1: Remote/local selector switch
SW2: ON/OFF switch
X, Y : Relay (Contactor rating DC 1 mA)
Sub
Lossnay
(Sub)
Lossnay
Lossnay
Lossnay
CO
sensor
CO
sensor
2
2
Group
CO
sensor
2
C-29