Download Print this page

Mitsubishi Electric Lossnay LGH-RX5-E Series Manual page 35

Advertisement

7.2
Electrical Wiring
Types of control cables
1. Wiring the M-NET transmission cables
• Types of transmission cables
Two-core shielded cable (CVVS, CPEVS).
• Diameter
1.25 mm
2
to 2.00 mm
2
• Maximum length from an end to the other end
Less than 200m
2. Remote controller
Type of cables
Diameter
Use 1.25~2.0mm
of exceeding 10m, and apply the rule of
Note
"7.3 Length of Control Cable" on the next
page.
ME remote controller
Two-core shielded cable
(MVVS)
0.5~0.75mm
2
2
cables for the portion
Lossnay remote controller
0.75mm
2
~1.25mm
2
MA remote controller
0.3~1.25mm
2
200m Max.
C-35

Advertisement

loading