Huawei UPS5000-H-400 kVA User Manual page 164

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
Table 11-6 Bypass input electrical specifications
Item
Power
system
Rated
voltage
Rated
frequency
Frequency
range
Input mode
Table 11-7 Battery electrical specifications
Item
Battery
voltage
(lead-acid
battery)
Battery cold
start
Charger
output power
Issue 02 (2021-04-22)
400 kVA/500 kVA/600 kVA/800 kVA
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2
Hz by default)
The mains input and bypass input share a power source (by
default) or use different power sources.
400 kVA/500 kVA/600 kVA/800 kVA
360–600 V DC
● 12 V batteries (30–50 batteries optional, 0 by default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 0.9
– 34–37 batteries: derated to 0.8
– 30–33 batteries: derated to 0.7
● 2 V batteries (180–300 batteries optional, 0 by default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 0.9
– 204–227: derated to 0.8
– 180–203: derated to 0.7
NOTE
The number of batteries is 0 by default and needs to be set based on
site requirements. Batteries have no neutral wire, and an odd number of
batteries are supported.
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
The maximum charge power is 15% of power of a single
module, and the charge current is limited to 30 A.
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
156