Huawei UPS5000-H-400 kVA User Manual page 27

Hide thumbs Also See for UPS5000-H-400 kVA:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
Figure 2-2 Typical application scenario of 1+1 parallel system
Dual-Bus System
A dual-bus system consists of two independent UPS systems. Each UPS system
consists of one UPS or multiple UPSs connected in parallel. Of the two UPS
systems, one is the master system and the other is the slave system. The dual-bus
system is highly reliable and is suitable for loads with multiple input terminals.
You can install an optional static transfer switch (STS) to start a bus
synchronization controller (BSC) provided in standard configuration. The UPS
systems work in inverter mode or bypass mode.
Figure 2-3 Typical application scenario of a dual-bus system consisting of single
UPS systems
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.
2 Product Overview
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-h-800kva

Table of Contents