Mitsubishi Electric MELSEC-Q Series User Manual page 219

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

APPENDICES
(2) System information
Number
Name
SM203 STOP contact
STOP state
SM204 PAUSE contact
PAUSE state
PAUSE enable
OFF: PAUSE disabled
coil
ON : PAUSE enabled
Device test
SM206
OFF: Device test not yet
request
acceptance
ON : Device test executed
status
Clock data set
OFF: Ignored
SM210
request
ON : Set request
OFF: No error
SM211 Clock data error
ON : Error
Clock data read
OFF: Ignored
SM213
request
ON : Read request
Communication
reserved time
OFF: Without delay
SM315
delay
ON : With delay
enable/disable
flag
(3) System clocks/counters
Number
Name
ON
SM400 Always ON
OFF
ON
SM401 Always OFF
OFF
ON
ON for 1 scan
SM402
OFF
only after RUN
ON
After RUN, OFF
SM403
for 1 scan only
OFF
0.05 sec.
SM410 0.1 second clock
0.1sec.
SM411 0.2 second clock
0.5 sec.
SM412 1 second clock
1 sec.
SM413 2 second clock
n sec.
SM414 2n second clock
User timing clock
SM420
No.0
User timing clock
SM421
No.1
User timing clock
SM422
No.2
User timing clock
SM423
No.3
User timing clock
SM424
No.4
App - 3
Meaning
• Goes ON at STOP state
• Goes ON at PAUSE state
• PAUSE state is entered if this relay is ON when the remote PAUSE
contact goes ON
• Comes ON when the device test mode is executed on GX
executed
Developer.
• When this relay goes from OFF to ON, clock data being stored from
SD210 through SD213 after execution of END instruction for changed
scan is written to the clock device.
• ON when error is generated in clock data (SD210 through SD213)
value, and OFF if no error is detected.
• When this relay is ON, clock data is read to SD210 through SD213
as BCD values.
• This flag is enabled when the time reserved for communication
processing is set in SD315.
• Turns ON to delay the END processing by the time set in SD315 if
there is no communication processing.
(The scan time increases by the period set in SD315.)
• Turns OFF to perform the END processing without a delay of the
time set in SD315 when there is no communication processing.
(Defaults to OFF)
Meaning
• Normally is ON
• Normally is OFF
• After RUN, ON for 1 scan only.
1 scan
• This connection can be used for scan execution type programs only.
• After RUN, OFF for 1 scan only.
1 scan
• This connection can be used for scan execution type programs only.
• Repeatedly changes between ON and OFF at each designated time
0.05 sec.
interval.
• When power supply is turned OFF, or reset is performed, goes from
0.1sec.
OFF to start.
Note that the ON-OFF status changes when the
0.5 sec.
designated time has elapsed during the execution of
the program.
1 sec.
• Goes between ON and OFF in accordance with the number of
n sec.
seconds designated by SD414.
• Relay repeats ON/OFF switching at fixed scan intervals.
n2
n2
• When power supply is turned ON, or reset is performed, goes from
scan
scan
OFF to start.
n1
• The ON/OFF intervals are set with the DUTY instruction.
scan
Special Relay List
Explanation
Explanation
DUTY
n1 n2 SM420
MELSEC-Q
Set by (When Set)
S (Status change)
S (Status change)
U
S (Request)
U
S (Request)
U
U
Set by (When Set)
S (Every END processing)
S (Every END processing)
S (Every END processing)
S (Every END processing)
S (Status change)
S (Status change)
S
(Every END processing)
App - 3