Mitsubishi Electric MELSEC-Q Series User Manual page 222

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

APPENDICES
(1) Diagnostic Information
Number
Name
SD0
Diagnostic errors Diagnosis error code
SD1
Clock time for
Clock time for
SD2
diagnosis error
diagnosis error
occurrence
occurrence
SD3
Error information
Error information
SD4
categories
category code
App - 6
Special Register List
Meaning
• Error codes for errors found by diagnosis are stored as BIN data.
• Contents identical to latest fault history information.
• Year (last two digits) and month that SD0 data was updated is stored as BCD 2-
digit code.
B15
to
Year (0 to 99)
• The day and hour that SD0 was updated is stored as BCD 2-digit code.
to
B15
Day (1 to 31)
• The minute and second that SD0 data was updated is stored as BCD 2-digit code.
B15
to
Minutes (0 to 59)
• Category codes which help indicate what type of information is being stored in the
common information areas (SD5 through SD15) and the individual information
areas (SD16 through SD26) are stored here.
• The common information category codes store the following codes:
0 : No error
1 : Unit/module No./ PLC No./Base No.
2 : File name/Drive name
3 : Time (value set)
4 : Program error location
• The individual information category codes store the following codes:
0 : No error
1 : (Open)
2 : File name/Drive name
3 : Time (value actually measured)
4 : Program error location
5 : Parameter number
6 : Annunciator number
Explanation
(Example)
B8
B7
to
B0
: October, 1995
Month (1 to 12)
H9510
(Example)
to
B8
B7
B0
: 10 p.m. on 25th
Hour (0 to 23)
H2510
(Example)
B8
B7
to
B0
: 35 min. 48 sec.
Seconds (0 to 59)
(past the hour)
H3548
to
B15
B8
B7
Individual information
Common information
category codes
category codes
MELSEC-Q
to
B0
Set by (When set)
S (Error)
S (Error)
S (Error)
App - 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qcpuMelsec q00jcpuMelsec q00cpuMelsec q01cpu

Table of Contents