Dismantling a system power supply module
The system power supply is wired up.
1. Turn off the fed supply voltage.
2. Open the front cover.
3. Shut down the system power supply.
4. Disconnect the power cable connector, and remove the connector from the system power
5. Undo the power supply module's fixing screw(s).
6. Swivel the system power supply out of the mounting rail.
Reference
Further information can be found in the Manuals for the system power supplies.
5.4
Mounting a load current supply module
Introduction
Load current supplies do not have a connection to the backplane bus of the S7-1500
automation systems and therefore do not use a configurable slot. The system power supply,
CPU, and input and output circuits of the I/O modules are supplied with 24 VDC through the
load current supply.
Requirements
The mounting rail is installed.
Tools required
Screwdriver with 4.5 mm blade
S7-1500 Automation System
System Manual, 02/2014, A5E03461182-AB
supply.
5.4 Mounting a load current supply module
Installation
53