Replica setting procedure for centralized busbar protection ied
Hide thumbs Also See for GRB200:
Table of Contents

Advertisement

among (i) to (iv), when CH1 is accounted in Replica.
[BayDevice_CH*]=Feeder: set '
Figure 2.1-3 Feeder setting when CH1 used
[BayDevice_CH*]=Coupler: set '
Figure 2.1-4 Coupler setting when CH1 used
For the coupler type, it is required for the user to enter a coupler number for
setting [Coupler No_CH*]. Remind that the same number must be entered on
both sides of the coupler, when two CHs are assigned for it. Figure 2.1-5
illustrates an example that the same coupler number '1' is set for CH1 and CH2;
similar means is employed for the other settings. As there is no rule for
numbering the CHs, so it is possible to choose preferred numbers for the CHs.
Busbar1
Busbar2
[BayDevice_CH*]=EndSection: set '
terminating a protection zone on the middle, as shown the below:
[Coupler No._CH3]=2
[Coupler No._CH4]=2
CH3
Coupler2
[Coupler No._CH2]=1
Coupler1
[Coupler No._CH1]=1
Coupler4
CH8
[Coupler No.8_CH]=4
[Coupler No._CH7]=4
Figure 2.1-5 Coupler number settings
- 4 -
feeder type
' when the bay is formed below:
coupler type
' when the bay is formed below.
CH4
4
Busbar3
[Coupler No._CH5]=3
Coupler3
[Coupler No._CH6]=3
Busbar4
CH7
end-section type
6F2S1923 (0.03)
' when the user wishes
GRB200C (Replica)
O
C
D
C
D
C
C