Step5: Zero Ampere Settings [Zacbycb_Ch*] - Toshiba GRB200 Instruction Manual

Replica setting procedure for centralized busbar protection ied
Hide thumbs Also See for GRB200:
Table of Contents

Advertisement

Step5: Zero ampere settings [ZACbyCB_CH*]

Zero-ampere control is required at the Coupler and the Section during the CB being open. The
Zero-ampere control can be performed by the acquisition of CB contact states. In the example,
the CH2 to CH6 are assigned at the Coupler and the Section; therefore On is set for settings
[ZABbyCB_CH2] to [ZABbyCB_CH6]. The other CHs are left with default Off setting.
Setting items
CH1
On
[CH use_CH*]
West
[CH name_CH*]
Feeder
Feeder
[BayDevice_CH*]
1(NA)
[Coupler No_CH*]
ZoneA
[Zone1_CH*]
ZoneB
[Zone2_CH*]
Non
[Zone3_CH*]
Non(NA)
[ZoneR1_CH*]
Non
[Zone-NoDIF_CH*]
DirConn
[CB_CH*]
[DS11_CH*]
NO, NC, Both
[DS12_CH*]
NO, NC, Both
Non
[DS13_CH*]
DirConn
[DS21_CH*]
Non
[Line1_CH*]
Non
[Line2_CH*]
Non
[Line3_CH*]
POS1
[CT-POS_CH*]
Off
[ZACbyCB_CH*]
Table 3.5-1 Settings on Step5
CH2
CH3
CH4
On
On
On
North
West Coupler
Section
Coupler
Coupler
1
2
ZoneA
ZoneB
ZoneC
Non
Non
Non
Non
Non
ZoneA
Non
Non
NO, NC or
NO, NC or Both
Both
NO, NC or
NO, NC or Both
Both
Non
Non
Non
Non
NO, NC or
Non
Both
Non(NA)
Non(NA)
Non(NA)
Non(NA)
Non(NA)
Non(NA)
POS1(NA)
POS1(NA)
On
On
- 25 -
CH5
CH6
CH7
On
On
On
South Section
East Feeder
Coupler
Feeder
3
1(NA)
ZoneB
ZoneD
ZoneC
Non
ZoneD
Non
Non
Non
Non(NA)
Non
Non
DirConn
NO, NC or Both
NO, NC, Both
NO, NC or Both
Non
NO, NC, Both
Non
Non
Non
DirConn
Non(NA)
Non
Non(NA)
Non
Non(NA)
Non
POS1(NA)
POS1
On
Off
6F2S1923 (0.03)
CH8 to CH24
Off
(no settings)
Non
1(NA)
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
Non
POS1
Off
GRB200C (Replica)