Toshiba GRB200 Instruction Manual page 14

Replica setting procedure for centralized busbar protection ied
Hide thumbs Also See for GRB200:
Table of Contents

Advertisement

Setting [ZACbyCH_CH*]
The setting is for Zero-ampere control. By this control, the value of flowing current will be
set 'Zero' unconditionally, when the CB is open in the CH. This control can operate when
On is set for the setting [ZACbyCH_CH*]. On the other hand, set Off when this is not
required. Remind that the user has to set either NO, NC, or Both for the setting [CB_CH*]
in order for this control.
[BayDevice_CH*]=Feeder:
Figure 2.1-8 illustrates Bay structure diagram about Feeder.
The user has to have settings: [Zone1], [Zone2], [Zone3], [DS11], [DS12], [DS13],
[DS21], [CB], [Line1], [Line2], and [CT-Pos]. The settings allow the user construct the
bay structure, which will be identical to a feeder bay drawn in Single line diagram.
Table 2.1-5 shows applicable settings in the feeder.
Zone1
Zone2
Zone3
DS
11
CB
[CT-Pos]=Pos1
DS
21
[CT-Pos]=Pos2
Figure 2.1-8 Bay structure diagram
of feeder
DS
DS
12
13
Line1
Line2
Line3
- 8 -
Table 2.1-5 Applicable setting in Feeder
Applicable setting
Setting items
(X means applicable)
Zone1_CH*
Zone2_CH*
Zone3_CH*
ZoneR1_CH*
Zone-NoDIF_CH*
CB_CH*
DS11_CH*
DS12_CH*
DS13_CH*
DS21_CH*
Line1_CH*
Line2_CH*
Line3_CH*
CT-Pos_CH*
ZACbyCB_CH*
6F2S1923 (0.03)
X
X
X
--
X
X
X
X
X
X
X
X
X
X
X
GRB200C (Replica)