Appendix 5.4.6; Parameter-Valid Drive And Boot File Setting - Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual

Table of Contents

Advertisement

Appendix 5.4.6

(1) Differences between High Performance model QCPU and Universal model
QCPU
(a) High Performance model QCPU
The parameter-valid drive is specified by the switches on the front panel of the High Performance model
QCPU.
(b) Universal model QCPU
The Universal model QCPU automatically determines the parameter-valid drive, depending on the existence of
parameters in the drive (program memory, memory card, SD memory card, or standard ROM).
Therefore, when replacing the High Performance model QCPU with the Universal model QCPU, changing the
boot file setting for parameter and/or moving files to another drive may be required.
When replacing the High Performance model QCPU with the Universal model QCPU, change the setting as
described below.
(2) Replacing High Performance model QCPU with Universal model QCPU
(a) When the parameter-valid drive is set to the standard ROM in the High Performance
model QCPU
Setting in High Performance model QCPU
Setting in the Boot file tab
of the PLC parameter dialog box
No boot file setting
Settings in the Boot file tab
Type
Transfer from
Program
Standard ROM Program memory
(No boot file setting for parameters)
Settings in the Boot file tab
Type
Transfer from
Program
Standard ROM Program memory
Parameter
Standard ROM Program memory

Parameter-valid drive and boot file setting

Change the setting so that the Universal model QCPU can refer to the
parameters in the standard ROM.
• Changes in parameter settings are not required.
• Delete parameters that exist in the program memory, memory card, and/or
SD memory card.
Change the setting so that programs are stored in the program memory in the
first place, instead of booting from the standard ROM.
• Delete all settings for parameter in the Boot file tab of the PLC parameter
Transfer to
dialog box.
• Delete parameters that exist in the program memory, memory card, and/or
SD memory card.
• Move the programs with boot setting into the program memory from the
standard ROM.
Change the setting so that programs and parameters are stored in the
program memory in the first place, instead of booting from the standard ROM.
Transfer to
• Move the programs and parameters with boot setting into the program
memory from the standard ROM.
• Delete all settings for parameter in the Boot file tab of the PLC parameter
dialog box.
Setting in Universal model QCPU
*2
*2
*1
*1
APPENDICES