Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual page 456

Table of Contents

Advertisement

Parameter
Item
IP Address Setting
Communication Data
Code
*1
Ethernet Conf.
/Open
Setting
FTP Setting
Time Setting
MELSOFT Connection
*1
Extended Setting
Network
Configuration
CC-Link
Setting
IEF Basic
*1
Setting
Refresh
Setting
Enable online change
(FTP, MC Protocol)
Disable direct connection
to MELSOFT
Do not respond to search
for CPU (Built-in Ethernet
port) on network
Simple PLC
communication function
IP packet transfer setting
*1
This setting item is available to the High-speed Universal model QCPU and Universal model Process CPU. Before
setting this item, check the versions of the CPU module and GX Works2 used. (
454
Description
No.
• IP Address:
Enter the IP address of the
CPU module.
• Subnet Mask Pattern:
Enter the subnet mask pattern
when using a router.
• Default Router IP Address:
Enter the IP address of the
router.
Select the code for MC protocol
1016
H
communication.
Set when using the following
functions.
• MC protocol
• MELSOFT connection
• Socket communication
• Predefined protocol
Set data when using the file
transfer function (FTP).
Set data when using the time
setting function.
Set data when using the
101F
MELSOFT connection extended
H
setting.
Set the network configuration
1030
when using CC-Link IE Field
H
Network Basic.
Set this parameter to refresh link
1031
device data to the internal device
H
or file register automatically.
Enable or disable writing data in
devices or files to the running
CPU module when MC protocol or
FTP is used.
Enable or disable direct
connection to MELSOFT.
To enhance the security with the
1016
H
remote password setting, check it
to disable it.
Checking this box disables
response to the find CPU function
of the MELSOFT connection.
To enhance the security, check it
to disable this.
Set parameters when using the
1019
simple PLC communication
H
function.
Set data when using IP packet
1016
H
transfer function.
Setting range
• IP Address:
0.0.0.1 to 223.255.255.254
(00000001
to 0DFFFFFFE
)
H
H
• Subnet Mask Pattern:
Blank or
192.0.0.0 to 255.255.255.252
(0C0000000
to 0FFFFFFFC
H
H
• Default Router IP Address:
Blank or
0.0.0.1 to 223.255.255.254
(00000001
to 0DFFFFFFE
)
H
H
Binary Code/ASCII Code
-
-
-
-
-
-
Selected/deselected
Selected/deselected
Selected/deselected
-
Use/Not used
Default
Reference
• IP Address:
192.168.3.39
• Subnet Mask
Pattern:
Blank
)
• Default Router
IP Address:
Blank
QnUCPU User's
Binary Code
Manual
(Communication
via Built-in
Ethernet Port)
Blank
Blank
Blank
Blank
Blank
CC-Link IE Field
Network Basic
Reference
Manual
Blank
Deselected
Deselected
QnUCPU User's
Manual
(Communication
via Built-in
Ethernet Port)
Deselected
-
Manual for the
CC-Link IE Field
Not used
Network module
used
Page 465, Appendix 2)

Advertisement

Table of Contents
loading

Table of Contents