Mitsubishi Electric MELSEC-Q00U(J)CPU User Manual page 49

Table of Contents

Advertisement

File type
Device comment
Initial device value
User setting area
File register
Sampling trace file
Device data backup file
Module error collection file
*4
Local device
Data logging setting file
System file for the iQ Sensor Solution
function (data backup/restoration)
Backup data file for the iQ Sensor
Solution function (data
backup/restoration)
Predefined protocol setting file
• CPU modules other than the High-speed Universal model QCPU and Universal model Process
CPU:
74 + 8 + (total comment data size of each device)
• High-speed Universal model QCPU and Universal model Process CPU:
74 + 72 + 8 + (total comment data size of each device)
Comment data size per device = 10 + 10240 × a + 40 × b
• a: Quotient of ((number of device points)/256)
• b: Remainder of ((number of device points)/256)
• CPU modules other than the High-speed Universal model QCPU and Universal model Process
CPU: 66 + 44 × n + 2 × m + 8
• High-speed Universal model QCPU and Universal model Process CPU: 66 + 44 × n + 2 × m +
72 + 8
• m: Total number of device points set to the initial device value
• n: Number of settings of the initial device value
Setting value when formatted (0 to 15K)
2 × (number of file register points)
362 + (number of word device points + number of bit device points) × 12 + (N1 + N2 + N3 +
number of word device points × 2 + (number of bit device points/16) × 2) × the number of traces
(total number of executions)
• Apply the following values to N1 to N3 according to the items selected under "Trace additional
Information" on the Trace condition settings window. (
• N1: When "Time" is selected, apply "4".
• N2: When "Step no." is set, apply "10".
• N3: When "Program name" is selected, apply "8".
Setting value when formatted (2 to 1024K)
76 + (64 × (value set for the number of storable errors))
70 + 6 × (set device type) + (Am + Av + B + Ct + Cst + Cc) × n
• Am, Av = (((a1 + a2) 16) -a11161× 2
• B = b × 2
• Ct, Cst, Cc = ((((c1 + c2) × 2)  16 - ((c1 × 2 + 1)  16) + 1) × 2 + c2 × 2
• Am, Av: Save area sizes of M (internal relay) and V (edge relay), respectively
a1: Start device number of M or V
a2: Number of points of M or V
• B: Save area size of D (data register) and Z (index register)
b: Total number of points of D and Z
• Ct, Cst, Cc: Save area sizes of T (timer), ST (retentive timer), and C (counter), respectively
c1: Start device number of T, ST, or C
a2: Number of points of T, ST, or C
• N: Number of programs (only the ones using local devices
Refer to the following.
QnUDVCPU/LCPU User's Manual (Data Logging Function)
Refer to the following.
iQ Sensor Solution Reference Manual
65532
CHAPTER 2 APPLICATION OF PROGRAMMING
File size (unit: byte)
Page 187, Section 3.14 (8) (b))
*5
)
2
47

Advertisement

Table of Contents
loading