Fault Test of each Zone
Once the test is commenced the Buzzer will rapidly turn on and off and the common Fault and Zone
Fault LED's will flash. Press Acknowledge, the Buzzer will be silenced and the common Fault and Zone
Fault LED's will continue to flash. Press Reset to return the panel to normal. The LCD will indicate the
Fault Test has been implemented on the selected Zone.
Fault Test Zone 1 Screen
Walk Test
IMPORTANT: The Brigade, Agent Release and any other system specific signalling should
be ISOLATED prior to initiating this test.
A Walk Test, sets the Zone to Non latching and allows the technician to test detectors and MCP's on that
Zone. When a detector or MCP is put into alarm the "Alarm Outputs" will operate, the corresponding
"Zone Alarm" LED will flash and the buzzer will sound.
The Zone will stay in Alarm until the MCP, or detector under test is reset or, the test is aborted by
pressing Cancel or, the test times out. The time out period can be set by pressing Enter once the Zone
has been selected and using the Move Up and / or Move Down keys to select the required time for
the test. The default time is 5 minutes but can be adjusted from 1 to 20 minutes by again using the
Move Up and / or Move Down keys to select the required time and then pressing Enter.
WLK TST
ZONE 1
Press
In the TEST END screen the operator has ten ( 10 ) seconds to enter the time before the test will
commence OR, the test can be started by pressing Enter.
Only one zone at a time can be in test mode, all other zones will operate as normal.
The LCD will display which Zone is the in Walk Test mode.
Enter
FLT TST
ZONE 1
TEST END
5 mins
Enter Time 
MAN1564-3
CANCEL
TO END
Enter