Level3: ( Pre-commissioning Password factory set at 3333 )
Level 3 SYSTEM and PROGRAM menus can only be accessed by a set Level 3 password that can not be
deleted.
Panels fitted with a key switch have access to level 2 with the switch enabled and then 3 via the
password. Without the key switch access to level 2 is by opening the door and then to level 3 via the
password.
Note: If the keypad controls are not used for a period of 2 minutes the display will return to the
default screen.

2.3 FireFighter Facility Controls

Note: Any of the buttons within the FireFighter Facility will act as a buzzer mute.
EXTERNAL
ALARM
ISOLATE
External Alarm Isolate Is a dedicated control used to isolate (turn off) the "External Alarms"
output and is not over ridden by any other condition. The LCD Screen will display the isolate
if the ISOLATES / OUTPUTS menu is selected.
WARNING
SYSTEM
ISOLATE
Warning System Isolate Isolates (turns off) the "Warning System" output and is not over
ridden by any other condition. The LCD Screen will display the WARNING SYSTEM is isolated
if the ISOLATE / OUTPUTS menu is selected.
ALARM
ACK
Acknowledge On Alarm the Alarm LED and Zone Alarm LED will flash and the Buzzer will
sound. By pressing Acknowledge the LED's become steady, the Buzzer will be silenced and a
zone/s can be Isolated or Reset.
FAULT
RESET
Reset The Reset is used to return the control panel back to a normal state from the fire alarm
condition. The Reset button is not to be used for any other purpose and will not reset an
isolated condition.
ISOLATED
ISOLATE
Isolate Isolates or De - isolates a Zone which has been selected using the Zone Select Menu.
Inhibits Alarm and Fault signalling outputs but not LED indications generated by the
corresponding zone. Isolates all acknowledged alarms in a single operation and operates the
fault buzzer if an isolate condition still exists on the panel after 8 hours. The LCD screens
below show an example.
ZONES
X
ISOL'D
Press
Isolated
ZONE 1
ZONE 3
ACTIVE
ACTIVE
Enter
Move Right
To Select Zone
ZONE 3
ISOL'D
Move Up
To Isolate
MAN1564-3
6