Buzzer
Press Enter to access the Sub – Menu then theMove Left orMove Right key to select either;
Resound, Alarm or Alarm Buzzer then Enter. Set the Resound, Alarm by using the Move Up key to
Yes (activate on alarm ) or Move Down key for No ( not activate on alarm ).
LED Annunciator Master ( LAM )
This tells the FACP how many LAMs are on the system hence how many to look for. Set the number by
using the Move Down and / or Move Up keys to increment to the desired number 0 to 8 (
maximum of 8 ).
LAM
8
Code
Code is the National Standard the Panel complies with. This is factory set and can not be altered.
CODE
AS4428
Back out to the Main Menu using the CANCEL key and move from the SYSTEMS Menu to the PROGRAM
Menu using the Move Right key. When the CANCEL key is pressed the LCD will display;
SYSTEM
ENABLED
RESOUND
YES
Resound Set to YES
for one second and all the Isolate LED's will be turned off.
ALARM
YES
Alarm Set to YES
MAN1564-3