Examples of the different " Styles " available through the Indicate Menu are shown above. Note only the
top display is shown in the first 2 examples where as the first 3 top displays are shown in Style 3
Once the "Style has been selected press Enter to update the Program and Cancel to back out of the
Menu
.
Display
To set the message, FACP or company name press Enter and use the Move Right and Move Left
keys to move through the word to select a letter and the Move Up and the Move Down keys to
move through the alphabet. A maximum of 16 characters are available for this message.
AMPAC
< INFO >
Press Enter to update each Program and Cancel to back out of the Menu.
Zone Labels
To name the Zones press Enter then the Move Right and / or the Move Left keys to select a Zone.
Press Enter and use the Move left and / or Move Right keys to move the cursor through the
structure of the word and the Move Up and Move Down keys to move through the alphabet.
Z LABELS
Press Enter to update each Program and Cancel to back out of the Menu.
EOL ( END OF LINE )
Press Enter and use the Move Up and Move Down keys to select the EOL option. The options are
CAP 10f, RES 3K3 ( AS factory default value ), 4K7, 6K8 and 10K.
EOL
CAP 10uF
Press Enter to update each Program and Cancel to back out of the Menu.
Zone S/C
Press Enter and use the Move Up or Move Down key to set the panel to initiate either an Alarm or
ZONE S/C
ALARM
Fault when a Zone short circuited condition exists.
Press Enter to update each Program and Cancel to back out of the Menu.
ZONE 1
EOL
RES 3K3
MAN1564-3
Z1 : LOBBY
EOL
RES 4K7
ZONE S/C
FAULT
28