Haier Ampac ZoneSense PLUS Operation Instructions Manual page 17

Table of Contents

Advertisement

Lamp Test
Press the Move Right and / or Move Left key to move to the Lamp Test menu, press Enter and each
LED on the panel will be sequentially turned on for one second and then off again. The Buzzer will sound
at the start and completion of the test.
Press
Enter
Note: The operator has to visually confirm each LED illuminates.
Battery Test
Press the Move Right and / or Move Left key to move to the Battery Test menu, Press Enter and the
Battery Test will commence, that is the Charger will be disconnected from the battery and a dummy
load placed across the battery for 60 seconds. The battery voltage should be above that specified ( 23.5
volts ) at the end of the testing period, if not a FAILED message is displayed.
BATT TST
26.1
Battery Test Underway
Sounder Tests of each SounderPress the Move Right and / or Move Left key to move to the
Sounder Test menu, press Enter, then select the Sounder by using the Move Up and / or Move
Down keys until the desired Sounder number is displayed, press Enter to start the test and Cancel to
turn it off.
Press
Enter
Back in the Main Menu From TEST Move Right to ISOLATES
LAMP TST
Indicates the Test Progress
SNDR TST
Sounder 6 Selected
LAMP >>>>>>
>>>>>>>>TST
BATT TST
PASS
Test Successful
SNDR TST
6
MAN1564-3
TEST...............
COMPLETE
Test Successful
BATT TST
FAIL
Battery Failure
Enter to Start
Cancel to Stop
17