6 Level 3 Access Programming

Level 3 is a technical level that allows a technician to;
➢ initialise the FACP so it is capable of recognising how the system is constructed; and SYSTEM
➢ program how it will present information as well as how it will react to a change of state of an input
and / or output.

6.1 Password Entry

Returning to Faults in the Main Menu, Move Right for Password Entry to Level 3. OR if entering the
programming from the Default Screen press the
Menu.
Press Enter and a flashing cursor will appear below the word PASSWORD. By using the Move up and
Move down keys the number on the screen will be incremented accordingly. Once the first password
number has been set use the Move right key to move to the next number to be set. This operation
has to be repeated four times as the PASSWORD is a four digit code. If a number is incorrect it can be
changed by using the Move Left and Right keys to position the cursor over the incorrect number.
Once the four numbers have been set pressing Enter initiates the verification of the PASSWORD that has
been entered. An incorrect PASSWORD will be displayed as REJECTED and return the operator to the
first menu of Level 1 access.
ENTER
PASSWORD
Press
Enter
If the PASSWORD is accepted the screen will display ACF TRIP RESET. Use the Right keys to move
through the menu to SYSTEM OR PROGRAM.
Note 1: The operator has 10 seconds to complete Password entry. Failure to enter the Password
in this time results in the panel reverting to the default screen.
Note 2: The System and Program Menus are not accessible if an Alarm condition exists even if
the correct Password is entered.
PROGRAM
Move Left key to directly access from the ACF Reset
PASSWORD
0000
Enter Password Correct Password Entry
MAN1564-3
PASSWORD
ACCEPTED
20