Hitachi Relion RES670 Commissioning Manual page 91

Phasor measurement unit
Hide thumbs Also See for Relion RES670:
Table of Contents

Advertisement

1MRK 511 409-UUS Rev. K
Table 12:
Test point
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
P12
P13
P14
Table 13:
Test point
P15
P16
P17
P18
P19
P20
P21
P22
P23
P24
P25
Table continues on next page
Phasor measurement unit RES670
Commissioning manual
Testing points to measure the outer boundary
R
0.0
0.8 * R1LIn + R1FInFw +
∆Fw
0.8 * (R1FInFw + ∆Fw)
RLdOutFw
R1FInFw + ∆Fw
0.8 * (R1FInFw + ∆Fw)
R1FInFw + ∆Fw
0.0
-(0.8 * R1LIn + R1FInRv +
∆Rv)
-0.8 * (R1FInRv + ∆Rv)
-RLdOutRv
-R1FInRv + ∆Rv
-0.8 * (R1FInRv + ∆Rv)
-(R1FInRv + ∆Rv)
Testing points to measure the inner boundary
R
0.0
0.8 * R1LIn + R1FInFw
0.8 * R1FInFw
RLdInFw
R1FInFw
0.8 * R1FInFw
R1FInFw
0.0
-0.8 * R1LIn + R1FInRv
-0.8 * R1FInRv
-RLdInRv
© 2017 - 2022 Hitachi Energy. All rights reserved
Testing functionality by secondary injection
X
Comment
X1OutFw
0.8 * X1OutFw
0.8 * (R1FInFw + ∆Fw) *
tan (ArgLd)
0.0
0.0
-0.8 * (R1FInFw + ∆Fw) *
tan (ArgLd)
-0.8 * X1OutRv
-X1OutRv
-0.8 * X1OutRv
-0.8 * (R1FInRv + ∆Rv) *
tan (ArgLd)
0.0
0.0
0.8 * (R1FInRv + ∆Rv) *
tan (ArgLd)
0.8 * X1OutFw
X
Comment
X1InFw
0.8 * X1InFw
(0.8 * R1FInFw + ∆Fw) *
tan (ArgLd)
0.0
0.0
-(0.8 * R1FInFw + ∆Fw) *
tan (ArgLd)
-0.8 * X1InRv
-X1InRv
-0.8 * X1InRv
-(0.8 * -R1FInRv + ∆Rv) *
tan (ArgLd)
0.0
Section 11
If OperationLdCh = Off
If OperationLdCh = Off
If OperationLdCh = Off
85