Multi-Range Function - Toshiba LF620F Instruction Manual

Electromagnetic flowmeter converter
Hide thumbs Also See for LF620F:
Table of Contents

Advertisement

10.3 Multi-range Function

Four types of multiple ranges shown below can be selected by setting the range type:
(1) Unidirectional flow, automatic selection of multiple ranges
(2) Bidirectional flows, automatic selection of multiple ranges
(3) Unidirectional flow, multiple ranges selected by external signal
(4) Bidirectional flows, multiple ranges selected by external signal
Proceed as follows to use the multi-range function.
Range setting
DO/DI setting
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Refer to 8.2.9, "Span (Range)" to set as follows:
1. Select the Range type.
2. Set the span for Ranges 1 to 4.
3. Set the Hysteretic value.
Refer to 8.2.18, "Digital Output" and 8.2.19, "Digital Input" to set Digital Output 1
(DO1) and/or Digital Output 2 (DO2) to use them as Range outputs.
To use the multiple ranges selected by external signal, set the Digital Input (DI) as a
switch to select the ranges.
- 116 -
6 F 8 A 0 9 2 8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lf622f

Table of Contents