● Changing the rate-of-change limit
The following is an example to change the rate-of-change limit value from 10.0% to 15.0%.
Switch operation
STEP1
STEP2
STEP3
STEP4(=END)
Note : If you try to set a value exceeding 30.0%, HIGH OVER SPEC error appears and the
value returns to the previous value. Set a value again.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Display example
D:FILTER
Select "LIM RATE" from the setting item
1 DAMPING
selection menu.
2 LIM RATE
3 LIM TIME
4 EXIT
ESC
LIM RATE
The currently set value (10.0% in this
example) appears.
10.0
Then push
%
ESC
LIM RATE
The switches at the bottom change.
(
10.0
At the same time, the cursor appears.
%
LIM RATE
Push
desired digit and push
15.0
number of the digit.
%
LIM RATE
When you push
to confirm whether the setting is OK or not.
15.0
If OK, push
setting, push
%
SET OK?
Pushing
and exits the setting screen.
ESC
O K
N O
- 75 -
6 F 8 A 0 9 2 8
Description
.
are shown.)
to move the cursor to the
to change the
, a message appears
O K
. If you want to redo the
N O
.
ESC
cancels the setting operation