Step 4: Login as Admin
From the Settings screen log in by pressing the Login Button (All Caps Username: ADMIN; Default Password: ADMIN)
Step 5: Update settings
Once logged in as the Admin user the following settings can be updated:
Ethernet IP Address, Subnet Mask
Modbus Node Type for one or each of the 5 drives can be entered in the corresponding Drop-down lists.
The reconnection pause in seconds (default is 1s). This setting controls how often the VFD-Gateway will check for a
loss of connection with a Node/drive on the Modbus RTU network. Example, if the value is programmed to 3
seconds and node/drive is powered down, the gateway will check every 3 seconds for this node/drive. A lower
setting will decrease the update speed of the VFD-Gateway when there is a problem with the Modbus RTU network.
The Ethernet IP Address, Subnet Mask, and the Gateway information can be entered into the corresponding white
boxes
The Modbus Node Type for one or each of the 5 drives can be entered in the corresponding Drop-down lists.
(ACS380, ACS580, ACH580, ACQ580, ACS880, DCS880, ACH580 E-Clipse, and ACS355)
Example: Selecting ACH580
from drop-down as Node 1