4.2 Troubleshooting steps
VFD-GATEWAY is not running
If gateway web interface is not accessible make sure the VFD-GATEWAY run light is illuminated green
VFD-GATEWAY is not accessible from known EtherNet/IP Address
Try the default IP address 192.168.0.10
Check Ethernet Connection between PC and VFD-GATEWAY
Check EtherNet/IP Address of PC.
Finally reset the VFD-GATEWAY by following the Factory reset steps (Refer to factory reset section 4.1)
Modbus connection troubleshooting:
Check Address for each Node
Drive baud rate is set to 38.4k baud.
Drive parity needs to be set to 8 Even 1
Check Modbus wiring (see page 7):
A1 on VFD-Gateway needs to be wired to B on VFD
B1 on VFD-Gateway needs to be wired to A on VFD
Make sure you use the correct cable
Termination resistors are in the correct place in the network
In ACS/ACH/ACQ/ACS880 and DCS880 products see 58.07 – Communication Diagnostics (refer to the Drive
manuals in each case)
58.08 Receive and 58.09 transmit
ACS355 – look at 53.06 – "OK Messages"
Use the Data screen in the VFD to see if we are transmitting data.
Drive Communicating but not running:
Check Start Stop Speed Reference (refer to drive set up page) for all drives
Make sure the control device is sending the correct information see ABB State Machine (refer to state machine
area of the drive manual)
Speed reference should follow the ABB speed reference specification (refer to speed reference area)
Check the correct drive is selected in the settings screen of the VFD-Manual
Use the Data screen in the VFD to see if we are transmitting data.
Make sure the Ethernet data mapping is correct for each drive (refer ethernet data section of manual)
Ethernet troubleshooting:
Make sure VFD-GATEWAY Ethernet IP address/Subnet mask/Gateway is programed correctly.
Make sure Ethernet Scanner device Ethernet IP address/Subnet mask/Gateway is programed correctly.
Check Ethernet Cable is properly connected
Make sure the Ethernet data mapping is correct for each drive (refer ethernet data section of manual)
If using a generic module make sure the assembly instance number and sizes are correctly programed (see
ethernet scanner setup section)