5.6 Technical Data
Power supply requirements (user supplied)
Voltage
Protection against reverse polarity
Current consumption
Environmental limits
Operating temperature (horizontal
mounting)
Operating temperature (vertical
mounting)
Storage temperature
Ambient Relative Humidity
Air pressure (operating)
Air pressure (storage)
Construction
Housing
Weight
IP Rating
EtherNet/IP Port
10/100BaseT(X) Port
Mode
CIP Gateway Objects Supported
Max. No. Of Adapter Connections
Input data size
Output data size
CIP Message Class Supported
Cable type
Serial interface
Serial standard
Baudrate
Data bits
Parity
Stop bits
Terminator for RS-485
Isolation
Serial signals
No of drive connections
ABB Drives supported
Cable type
Communication speeds
Typical read time
Continuous read/write time.
The VFD-Gateway is set up to only write data to the drive when the write
data changes, this allows us to optimize communication speed.
Standards and certifications
cUL, CE and RoHS
Package contents
Device
Modbus RTU
Terminal block
Documentation
For more information please contact
your local ABB representative or visit:
www.abb.com/drives
24 VDC (-15 %, +20 %)
Yes
340mA Max
0 °F... +140°F (0 °C...+60 °C)
0 °F... +104°F (0 °C...+40 °C)
-40°F... +158°F (-40 °C...+70 °C)
Max. 95 %, without condensation
> 800 hPa / < 2000 m
> 800 hPa / < 2000 m
Plastic, Classification V0 according to UL 94
0.88lb (0.4kg)
IP20
1 – Auto/10/100 - RJ45 connection
Adapter
Identity, Message Router, Assembly,
Connection Manager, Ethernet link,
Port
100
150 bytes
150 bytes
Class 1 or I/O messages; Class 3 or
Explicit message are not supported
CAT5 or higher, and type UTP, FTP or STP
RS-485 (Modbus RTU)
38,400 bps
8
Even
1
120 ohms, ¼ watt (Built In)
2kV (Built In)
RS-485 2 wire
Up to 5 (max)
ACS355 (limited support)
ACH580 E- Clipse (limited support)
ACS180; ACS380; ACS480; ACS580,
ACH580; ACQ580; ACS880; DCS880
2 cores, twisted, with common shield (see
manual Modbus installation section for full
requirements)
60-70ms per drive
100 -110ms per drive
1 x VFD-GATEWAY
1 x TA5142 RTU RS485 adapter
1x 3 pin spring loaded terminal block
1 x 12 pin spring loaded terminal block 1 x
13 pin spring loaded terminal block
1 x quick installation guide
1 x warranty card
We reserve the right to make technical changes or modify
the contents of this document without prior notice. With
regard to purchase orders, the agreed particulars shall
prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject
matter and illustrations contained therein. Any
reproduction, disclosure to third parties or utilization of its
contents – in whole or in parts – is forbidden without prior
written consent of ABB.
Copyright© 2022 ABB. All rights reserved.

Advertisement

loading

This manual is also suitable for:

Vfd-gateway