Error Code
Indoor unit setting not performed/deleted
Air conditioner gives ER 05 error.
Type code of the air conditioner is
deleted.
*
(
) Refer to 12.4 setting with remote control page 56
Error Code
Communication error
Indoor unit gives ER 06 error (Indoor
and outdoor unit)
Are there cross connections in
interconnection cables?
Check the product codes. Is there a
pairing problem?
Check the terminal connections and
the suitability of electrical installation.
Are there any loose connections, loose
contacts, etc?
Disconnect all connection cables going
from the indoor unit terminal to the
outdoor unit and short-circuit the clips
no. 2 and 5 with an appropriate cable.
Press the force start button to give
energy. At the end of the test, if the
board is malfunctioned, it will give an
error code; if it is okay, it will give 00.
Replace the outdoor unit control board.
(7 Segment)
ER 05
(7 Segment)
ER 06
NO
NO
NO
NO
Outdoor unit led
(*)
Manually do setting via the remote
control after getting support from the
product support unit about the setting
code.
Board must never be
Outdoor unit led
Blinking 9 times - stopping for 3 sec.
Outdoor unit LED gives 9 signals
(Outdoor unit signal error)
YES
Check the connections again, correct if
there is any connection error.
YES
Replace indoor unit or outdoor unit
according to indoor unit and outdoor
unit pairing codes.
YES
Resolve the impropriety.
YES
Replace the indoor unit control board.
31
replaced.