56 Technical data
Derating
Surrounding air temperature derating
■
In the temperature range +45...55 °C (+113...131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor
(k) :
k
1.00
0.95
0.90
+45 °C
+113 °F
Coolant temperature derating
■
See ACS880-107LC inverter units hardware manual (3AXD50000196111 (English)).
Fuses
ACS880-
7107LC-...
Qty
0350A-7
2
0550A-7
2
0750A-7
2
0950A-7
2
1100A-7
4
1500A-7
4
1900A-7
4
1650A-7
6
2250A-7
6
2850A-7
6
T
+55 °C
+131 °F
DC fuses
A
V
500
1250
800
1250
1100
1000
1400
1100
800
1250
1100
1000
1400
1100
800
1250
1100
1000
1400
1100
Manufacturer
Bussmann
170M6542
Bussmann
170M6546
Bussmann
170M6549
Bussmann
170M6501
Bussmann
170M6546
Bussmann
170M6549
Bussmann
170M6501
Bussmann
170M6546
Bussmann
170M6549
Bussmann
170M6501
Type