Dimensions And Weights; Free Space Requirements; Losses, Internal Cooling Circuit Data And Noise - ABB ACS880-7107LC Hardware Manual

Dc feeder units
Hide thumbs Also See for ACS880-7107LC:
Table of Contents

Advertisement

Dimensions and weights

Height
ACS880-
7107LC-...
mm
0350A-7
2002
0550A-7
2002
0750A-7
2002
0950A-7
2002
1100A-7
2002
1500A-7
2002
1900A-7
2002
1650A-7
2002
2250A-7
2002
2850A-7
2002

Free space requirements

The values are as required by cooling, maintenance and/or operation of the pressure
relief (if present). Also obey the general mechanical installation instructions.
Front
mm
1000

Losses, internal cooling circuit data and noise

ACS880-
P
total
loss
7107LC-...
kW
0350A-7
0.03
0550A-7
0.2
0750A-7
0.6
0950A-7
0.9
1100A-7
0.6
1500A-7
1.1
1900A-7
1.8
1650A-7
0.9
2250A-7
1.7
2850A-7
2.7
Width
mm
400
400
400
400
500
500
500
700
700
700
in.
mm
39
0
Losses
P
P
loss coolant
loss air
kW
kW
0.02
0.01
0.1
0.1
0.4
0.2
0.6
0.3
0.4
0.2
0.8
0.4
1.2
0.6
0.6
0.3
1.1
0.6
1.8
0.9
Depth
mm
644
644
644
644
644
644
644
644
644
644
Sides
in.
0
Liquid quantity
Total
Mass flow
l
l/min
2.6
7.2
2.6
7.2
2.6
7.2
2.6
7.2
3.4
7.2
3.4
7.2
3.4
7.2
7.0
13.6
7.0
13.6
7.0
13.6
Technical data 57
Weight
kg
250
250
250
250
320
320
320
435
435
435
Above
mm
in.
250
9.85
Noise level
Pressure
Average
loss
kPa
dB(A)
120.0
63
120.0
63
120.0
63
120.0
63
120.0
63
120.0
63
120.0
63
120.0
66
120.0
66
120.0
66

Advertisement

Table of Contents
loading

Table of Contents