Fuses - ABB ACS800-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

Fuses

gG and aR fuses for protection against short circuit in the input power cable or drive
are listed below. Either fuse type can be used if it operates rapidly enough. Choose
between gG and aR fuses according to the table under
between gG and aR fuses
the short-circuit current of the installation is at least the value given in the fuse
table. The short-circuit current can be calculated as follows:
I
k2-ph
where
I
= short-circuit current in symmetrical two-phase short circuit (A)
k2-ph
U
= network line-to-line voltage (V)
R
= cable resistance (ohm)
c
2
Z
U
S
= z
·
/
k
k
N
z
= transformer impedance (%)
k
U
= transformer rated voltage (V)
N
S
= nominal apparent power of the transformer (kVA)
N
X
= cable reactance (ohm).
c
,
(page 109)
U
=
2
2 ·
R
+ (Z
c
= transformer impedance (ohm)
N
Quick guide for selecting
or verify the operating time by checking that
2
+ X
)
k
c
Technical data 103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04mAcs800-u4

Table of Contents