ABB ACS800-04 Hardware Manual page 134

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

134 Resistor braking
ACS800-04
Fram
Braking power of the chopper
type
e size
and the drive
5/60 s
P
(kW)
690 V units
-0140-7
R7
125
-0170-7
R7
125
-0210-7
R7
125
-0260-7
R7
135
-0320-7
R8
300
-0400-7
R8
375
-0440-7
R8
430
-0490-7
R8
550
-0550-7
R8
550
-0610-7
R8
550
P
Maximum braking power of the drive with the specified resistor(s). The drive and the chopper
br5
withstand this braking power for 5 seconds per minute.
P
The drive and the chopper withstand this braking power for 10 seconds per minute.
br10
P
The drive and the chopper withstand this braking power for 30 seconds per minute.
br30
P
The drive and the chopper withstand this continuous braking power. The braking is
brcont
considered continuous if the braking time exceeds 30 s.
Note: Make sure that the braking energy transmitted to the specified resistor(s) in 400 seconds does
E
not exceed
.
R
R
Resistance value for the resistor assembly.
Note: This is also the minimum allowed resistance for the brake resistor.
E
Short energy pulse that the resistor assembly withstands every 400 seconds. This energy
R
heats the resistor element from 40 °C (104 °F) to the maximum allowable temperature.
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy
Rcont
dissipates in 400 seconds.
*
ACS800-Ux types only
1)
240 kW possible if ambient temperature is below 33 °C (91 °F)
2)
160 kW possible if ambient temperature is below 33 °C (91 °F)
3)
630 kW possible if ambient temperature is below 33 °C (91 °F)
4)
450 kW possible if ambient temperature is below 33 °C (91 °F)
5)
135 kW possible if ambient temperature is below 33 °C (91 °F)
6)
148 kW possible if ambient temperature is below 33 °C (91 °F)
7)
160 kW possible if ambient temperature is below 33 °C (91 °F)
10/60
30/60
s
s
br5
P
P
br10
br30
(kW)
(kW)
110
90
5)
110
90
6)
110
90
6)
120
100
7)
300
300
375
375
430
430
400
315
400
315
400
315
Brake resistor(s)
Type
P
brcont
(kW)
75
SAFUR80F500
75
SAFUR80F500
75
SAFUR80F500
80
SAFUR80F500
260
SAFUR200F500
375
SAFUR200F500
385
SAFUR200F500
225
2xSAFUR125F500
225
2xSAFUR125F500
225
2xSAFUR125F500
P
R
E
R
Rcont
(ohm)
(kJ)
(kW)
6.00
2400
6
6.00
2400
6
6.00
2400
6
6.00
2400
6
2.70
5400
13.5
2.70
5400
13.5
2.70
5400
13.5
2.00
7200
18
2.00
7200
18
2.00
7200
18
00096931