ACS800-U4
Input
type
current
-0320-7
273
-0400-7
325
-0440-7
370
-0490-7
407
-0550-7
463
-0610-7
513
Thermal overload and short-circuit protection
Note 1: See
Note 2: In multi-cable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve
of the fuse does not exceed the melting curve of the fuse mentioned in the table.
A
A
500
500
500
600
600
700
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Ferraz
(page 46).
Technical data 117
Type
UL class
JJS-500
T
JJS-500
T
JJS-500
T
JJS-600
T
JJS-600
T
A4BY700
L