First Environment (Drive Of Category C2); Second Environment (Drive Of Category C3) - ABB ACS800-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

126 Technical data

First environment (drive of category C2)

The drive complies with the standard with the following provisions:
1.
The drive has EMC filter +E202.
2.
The motor and control cables are selected as specified in the hardware manual.
3.
The drive is installed according to the instructions given in the hardware manual.
4.
Maximum cable length is 100 m.
WARNING! The drive can cause radio interference if it is used in a residential
or domestic environment. The user is required to take measures to prevent
interference, in addition to the requirements for CE compliance listed
above, if necessary.
WARNING! Do not install a drive with EMC filter +E202 on IT (unearthed)
systems. The supply network becomes connected to earth potential
through the EMC filter capacitors which can cause danger or damage the
unit.

Second environment (drive of category C3)

The drive complies with the standard with the following provisions:
1.
The drive has EMC filter +E210. The filter is suitable for TN (earthed) and IT
(unearthed) systems.
2.
The motor and control cables are selected as specified in the hardware manual.
3.
The drive is installed according to the instructions given in the hardware manual.
4.
Maximum cable length is 100 m.
WARNING! A drive of category C3 is not intended to be used on a low-
voltage public network which supplies domestic premises. Radio frequency
interference is expected if the drive is used on such a network.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-04mAcs800-u4

Table of Contents