4.3.4

Terminal DA1 response level adjustment (Pr.839)

• The response level of the output voltage of the terminal DA1 can be adjusted between 0 and 5 s with Pr.839.
• Increasing the setting stabilizes the terminal DA1 output more but reduces the response level.
NOTE
• Response time of the terminal DA1 is a total of the set value in Pr.839 DA1 output filter and a variable (up to 5 ms).
• When Pr.839="0", the instantaneous values are monitored for the following items.
Pr.838
Types of monitor
6
Running speed
7
Motor torque
17
Load meter
32
Torque command
33
Torque current command
Torque monitor
36
(driving/regenerative polarity switching)
• Pr.1106 Torque monitor filter and Pr.1107 Running speed monitor filter are disabled to terminal DA1 output.
26
BIPOLAR ANALOG OUTPUT