Motor Temperature Detection Signal - Mitsubishi Electric 800 Series Instruction Manual

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

6.3.5

Motor temperature detection signal

When motor temperature exceeds the detection level, motor temperature detection signal (Y55) is output. (Set Pr.407 Motor
temperature detection filter  "9999")
Set "55 (positive logic)" or "155 (negative logic)" in the following parameters to output the motor temperature detection signal
(Y55) when motor temperature exceeds the detection level.
• Pr.190 to Pr.196 Output terminal function selection (Refer to the Instruction Manual (Detailed) of the inverter for details.)
• Pr.313 to Pr.319 DO0 to DO6 output function selections (Refer to the Instruction Manual of FR-A8AY for details.)
• Pr.320 to Pr.322 RA1 to RA3 output function selections (Refer to the Instruction Manual of FR-A8AR for details.)
Pr.
Pr. group
*1
M061
750
*1
Setting can be made only when the FR-A8AZ is mounted.
NOTE
• The motor temperature detection signal is not available when Pr.407 = "9999".
44
MOTOR THERMISTOR INTERFACE
Name
Motor temperature detection level
Pr.750
OFF
Y55
Setting range
0 to 200
Hysteresis range (5°C)
Motor temperature
Time
ON
OFF
Y55 signal turns OFF when motor temperature
become Pr.750 or less (with hysteresis).
Minimum
setting
Initial value
increments
1
75