NOTE:
If there are several patterns of the same input channel and interlock operation conditions,
the interlock control operation will be output in the ascending order of the interlock operation
No.
Note the order when setting the same interlock operation conditions patterns.
To output several interlock control operations under the same input interlock operation conditions,
make the following settings.
E.g.)
<Input interlock operation condition>
[Ch No.] 1
When following three interlock control operations are output
under the above interlock operation condition.
<Interlock control operation output>
[Interlock target] 001 (Indoor unit: address 01)
The interlock control is output in the following order.
[ON/OFF]
[Mode]
[Set temp.]
[Interlock No.] 1
[Interlock No.] 2
[Interlock No.] 3
The interlock control operation is output in the order of No.1, 2 and 3.
The interlock control No. does not have to be consecutive;
however it is recommended to set the consecutive No. to avoid mistakes in the setting.
[Interlock operation conditions]
Operation, Interlocked LOSSNAY unit: Run (Low)
Cool
25°C
[Ch No.] 1
[Interlock operation conditions] Error occurrence
[Interlock target] 001 [ON/OFF] Operation,
[Ch No.] 1
[Interlock operation conditions] Error occurrence
[Interlock target] 001 [Mode] Cool
[Ch No.] 1
[Interlock operation conditions] Error occurrence
[Interlock target] 001 [Set temp.] 25°C
Error occurrence
Interlocked LOSSNAY unit: Run (Low)
101