Mitsubishi Electric MN converter Operating Manual page 111

Electric air-conditioner network system
Hide thumbs Also See for MN converter:
Table of Contents

Advertisement

NOTE:
If there are several patterns of the same input channel and interlock operation conditions,
the interlock control operation will be output in the ascending order of the interlock operation
No.
Note the order when setting the same interlock operation conditions patterns.
To output several interlock control operations under the same input interlock operation conditions,
make the following settings.
E.g.)
<Input interlock operation condition>
[Ch No.] 1
When following three interlock control operations are output
under the above interlock operation condition.
<Interlock control operation output>
[Interlock target] 001 (Indoor unit: address 01)
The interlock control is output in the following order.
[ON/OFF]
[Mode]
[Set temp.]
[Interlock No.] 1
[Interlock No.] 2
[Interlock No.] 3
The interlock control operation is output in the order of No.1, 2 and 3.
The interlock control No. does not have to be consecutive;
however it is recommended to set the consecutive No. to avoid mistakes in the setting.
NOTE:
When you use Fahrenheit for the unit, there might be differences of the plus or minus 0.1 °F in the set
value and the value monitored after it sets it.
[Interlock operation conditions] Input value>25°C
Operation, Interlocked LOSSNAY unit: Run (Low)
Cool
23°C
[Ch No.] 1
[Interlock operation conditions]
[Interlock target] 001 [ON/OFF] Operation,
[Ch No.] 1
[Interlock operation conditions]
[Interlock target] 001 [Mode] Cool
[Ch No.] 1
[Interlock operation conditions]
[Interlock target] 001 [Set temp.] 23°C
Interlocked LOSSNAY unit: Run (Low)
110
Input value>25°C
Input value>25°C
Input value>25°C