<Interlock special condition setting>
[Emergency stop receive: Interlock disable]
When the emergency stop command is received from G(B)-50A, whether to enable or disable the
interlock operation depending on the change in input contact status can be set for each channel.
* The pressed (sunken) button shows the currently "Disable" status.
The interlock operation will be disabled for 15 minutes on the input channel on which "Disable" is
set after the emergency stop command is received from G(B)-50A.
Unless the emergency stop command is received again within 15 minutes, the "Interlock disable"
will be inactive after 15 minutes have passed.
For your safety, "Disable" is set (default) to all channels. However, the setting can be changed
on the unit that is required to be run at emergency. Consider carefully how the unit is required
to be run at emergency, and make the proper setting.
Emergency stop receive:
Interlock disable setting
Input channel
Change in input
contact status
[SC communication error detection: Interlock disable]
When the communication error with G(B)-50A occurs, whether to enable or disable the interlock
operation depending on the change in input contact status can be set for each channel.
* The pressed (sunken) button shows the currently "Disable" status.
The interlock operation will be disabled on the input channel on which "Disable" is set when the
communication error with G(B)-50A occurs.
When the communication error with G(B)-50A is reset, the "Interlock disable" will be inactive.
For your safety, "Disable" must be set when no means (such as local remote controllers) is
available to stop the operation of the interlock target unit.
SC communication error detection:
Interlock disable setting
Input channel
Change in input
contact status
Ch1
Disable
Controller
Ch2
Disable
Ch3
Ch1
Disable
Controller
Ch2
Disable
Ch3
M-NET
Emergency stop command
DIDO
(66DC)
M-NET
Communication error
DIDO
(66DC)
98
G(B)-50A
Interlock operation
G(B)-50A
Interlock operation