Error #241:
Txintrc or Rxintrc was called with invalid type %%
Invalid parameter type. See Intrac Protocols chapter in Advanced Features in
the Application Programmer manual.
Error #242:
Intrac/Meic port not created
The appropriate port must be defined in Site Configuration.
Error #243:
One of the following calls: Txintrc, Txwidth, Rxintrc, Rxwidth, Rxiupd failed
getting pointer to value at intrac system table
May indicate system software problem. Consult product group.
Error #244:
Txintrc was called with ITxStt=0 or Txwidth was called with Tx_len=0
Illegal value set in application.
Error #245:
#the 'Load' option was used to download the application, however the number of
diffrentiators were changed.
You should use the 'Reset Load' option instead and then do Download.
Error #250:
Cannot read module type at: %%
I/O module defined but physically missing.
Error #251:
Module type does not match site configuration, module: %%
Incompatible module type. Configuration definition and physical module are
different.
Error #252:
Module: %%, initial values are invalid.
There are no preset values in the control registers of the DO module gate array.
Error #253:
Digital output module: %%, desired values in gate array are not equal to image
in memory.
The gate array data and the image in the RTU do not match.
Error #254:
Digital output module: %%, actual values of relays are not equal to desired
values in gate array.
The gate array data and the image in the RTU do not match.
Error #255:
I/O module: %% analog input not calibrated.
At least one of the analog input in the module is not calibrated.
Error #256:
Cannot 'communicate' with module: %%
It is not possible to read data from the module; it is faulty.