If none of the ports is defined as RS232 Local Computer, ToolBox access will be permitted
through any port, provided it is defined as MDLC. If there is no such port, access will be
denied. You may reset the configuration of the IP Gateway using the 'Erase Configuration'
operation in the Downloader application.

Upload

The Upload command is used to read the site configuration from the IP Gateway into the
ToolBox. You can upload from the IP Gateway directly connected to the ToolBox computer,
or from a remote IP Gateway.
Before you activating the Upload command:
Make sure that the OutPutBar is displayed.
Make sure that the SiteIDBar is displayed and the address is configured properly.
Make sure that the ToolBox computer is ready to communicate.
Use the SiteIDBar to specify the IP Gateway to which the site configuration file is to be
uploaded.
SiteIDBar parameters
Local
If the ToolBox computer is locally connected to the IP Gateway, make sure that this parameter
is selected.
Remote
If you want to upload the configuration of a remote site, click this parameter.
Site ID, Link ID
If you want to upload the configuration of a remote site, specify its Site ID, open the Link ID
drop-down list and select the appropriate link ID. If a configuration created with an earlier
version of ToolBox is uploaded, a message box appears which is similar to the one that
displays when you activate the Open command for an older configuration. See details in Open,
earlier in this chapter.
After specifying the IP Gateway in the SiteIDBar, click on the Upload icon or select Upload
from the File menu. The ToolBox will ask you to specify the communication password. After
the correct password is entered, ToolBox will begin uploading the configuration file. The
upload information will be displayed in the OutPutBar Upload Tab. After the upload
operation ends successfully, the ToolBox displays useful status information in the Upload
Information dialog box, as illustrated below.