ABB RER601 Technical Manual page 54

Wireless gateway
Hide thumbs Also See for RER601:
Table of Contents

Advertisement

Section 5
RER601/603 Configurator
48
GUID-34F79C50-5936-4073-ACB1-DA674755FEC5 V1 EN
Figure 32:
Network settings
Network protocol defines the network transmission layer protocol (either TCP or
UDP) used with IEC 60870-5-104 network communication. The IEC 60870-5-104
standard protocol uses TCP, but for reliable slow-speed packet-switched networks
the UDP protocol can be used to minimize the packets transmitted over network.
Table 13:
Network protocol in IEC 60870-5-104 communication
Description
Type
Units
Value range
Note
Network port to listen defines the network port to listen for incoming IEC
60870-5-104 connections.
Table 14:
TCP or UDP port to listen for incoming IEC 60870-5-104 connections
Description
Type
Units
Value range
Note
Network idle timeout defines the idle time-out of the network connection in
seconds. If there is no network data received during the specified interval, the
device closes the connection. This parameter is required to detect partially closed
connections and to release the resources for new connections, especially if the New
connection priority parameter is disabled. The value "0" disables the network idle
time-out detection.
Table 15:
Network idle time-out for IEC 60870-5-104 connections
Description
Type
Units
Value range
Note
Value
Network transmission layer protocol
N/A
UDP, TCP
The IEC 60870-5-104 standard specifies only the
TCP protocol
Value
Network port
Port number
0...65000
The IEC 60870-5-104 standard specifies TCP
port 2404
Value
Time-out
Seconds
0...65000
The network idle time-out must be longer than
the IEC 60870-5-104 link test interval (t3)
1MRS757105 B
RER601/603
Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer603

Table of Contents